|
|
|
|
|
|
| A drawback associated with having a reactive voltage-sampling network at the transmitter side of an impedance monitoring bridge is that it leaves the generator with a reactive load when the bridge is balanced. In US Patent No. 2734169, Douma offers a solution to this problem which involves producing a correction voltage to be added to the sum of the bridge current and voltage analogs . The situation which Douma considered is illustrated below (note that current-transformer secondary stray capacitance and propagation delay are neglected in the derivation which follows): |

|
In this case there is a capacitance Ca
permanently connected across the generator, causing a phase-shift
which cannot be taken into account when ZL
is adjusted to balance the bridge. We can however envisage a
situation in which the system is somehow adjusted to make the
generator see a pure resistance R0; in
which case, presuming that the voltage-sampling impedance Z1+Z2 is sufficiently
large to be neglected (or is actually responsible for the capacitance
Ca), and that the current
transformer insertion impedance is sufficiently small to be neglected,
R0 will be the parallel combination of
ZL and the impedance of the capacitor
Ca, i.e.: R0 = ZL // jXCa which can be written: 1/R0 = (1/ZL) + (1/jXCa) and so the load admittance will be: 1/ZL = (1/R0) - (1/jXCa) The output of the bridge will be:
I = V' / ZL = V' [ (1/R0) - (1/jXCa) ] hence:
Vcorr = -V' (Ri // jXLi) / ( jXCa Ni ) It will take quite an elaborate network to obtain exactly this voltage, but Douma made the sensible observation that the capacitance Ca will generally be small, since the main use of the correction is to cancel the effect of using a capacitive voltage-sampling network at the generator side of the bridge. Hence Ca will only cause a serious shift in load phase angle at high frequencies, and the correction voltage at low frequencies will be negligible. It is therefore legitimate to assume that significant correction will only occur when XLi>>Ri, and hence Ri//jXLi»Ri , and so the simplified correction voltage becomes: |
|
Vcorr = -V' Ri
/ ( jXCa
Ni ) Now consider the voltage divider circuit on the right. Its output is: Vcorr = V' Rb / (Rb + jXCb) but if XCb>>Rb, this expression becomes to a good approximation: Vcorr = V' Rb / (jXCb) If we now choose Cb to be the same as Ca, then setting Rb=Ri/Ni gives the required correction voltage, except that the sign should be negative (phase reversal is required). |
![]() |
| That the approximation XCb>>Rb can be made to hold good can be seen by considering that Ri is typically about 50W and Ni is usually in a range from 10 to 40 turns. Therefore Rb will never be greater than about 5W, whereas the input-side capacitive voltage-sampling network for which Ca is a model will typically have a reactance of around -400W at the highest frequency of operation, and this will only increase in magnitude at lower frequencies. The only remaining problem is that the correction voltage derived by the RC network is of the wrong polarity, and needs to be floating with respect to ground so that it can be added into Vdet. This calls for the use of a 1:1 isolation transformer, which is shown in Douma's final circuit below: |

|
Note that the resistor Rb
is connected to the secondary side of the transformer. This is
done so that the transformer magnetising current (i.e., the current
which flows because the inductance of the transformer is not
infinite) is small in comparison to the current which flows due
to the presence of the resistor. The resistor in this position
will also damp any transformer resonances. This ensures that
the phase of the current flowing out of the secondary is very
close to 180° relative to the phase of the current in the
primary, thereby establishing the required 90° difference
between Vcorr and V' to
the best possible approximation. If we assume that RV>>XC1 at high frequencies, the capacitance at the generator side of the bridge will be, to a good approximation, C1C2/(C1+C2). If we set Rb=Ri/Ni, and adjust ZL (using an auxiliary bridge) so that the generator sees R0, adjusting Cb will bring the bridge to balance at high frequencies when Cb=C1C2/(C1+C2). The importance of Douma's correction method for generator-side reactance lies in the fact that it introduces the idea of obtaining bridge-balance by performing summations other than the generic Vv-Vi=0. This is the key to making bridges which monitor only a single scalar attribute of a load impedance, such as its resistance or conductance. Douma's method also instructive in its use of a quadrature network, and of a transformer as a voltage sampling network. What is extraordinary however, is that it represents several missed opportunities. Douma used a transformer as a voltage sampling device, but did not invent the transformer voltage-sample bridge. Douma was fully conversant with the problem of generator power-factor error and displayed great ingenuity in overcoming it; but it did not occur to him that the solution might be simply to move the voltage sampling network to the other side of the current transformer, or to include a small compensating inductance in series with the generator. |
|
|
|
|
|
|